← NRC enforcement actions

NRC CAL – NOV (White)

EA-09-167 · CAL · Issued 2009-09-03 · Reactor Licensees

Action

EA Number
EA-09-167
Licensee
NOV (White)
Category
Reactor Licensees
Action type
CAL
Date issued
2009-09-03

Description

On September 3, 2009, a Notice of Violation was issued to Northern States Power Company - Minnesota for a violation associated with a White Significance Determination Finding involving a violation of 10 CFR Part 50, Appendix B, Criterion III, "Design Control" which requires, in part, that measures be established to assure that the design basis for safety related functions of structures, systems, and components are correctly translated into specifications, drawings, procedures, and instructions. Contrary to this requirement, Prairie Island Nuclear Generating Plant failed to implement design control measures to ensure that the design basis for the component cooling water system was correctly translated into specifications, drawings, procedures, and instructions. Specifically, the licensee failed to ensure that the safety-related function of the component cooling water system was maintained following a high energy line break, seismic, or tornado events in the turbine building.

Source

Full letter
PDF on NRC ADAMS
NRC index
Reactor Licensees enforcement actions
Machine
JSON-LD · Markdown